Sign In | Join Free | My burrillandco.com
Home > Impulse Voltage Generator >

High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing

Sansion Power Electric Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing from wholesalers
     
    Buy cheap High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing from wholesalers
    • Buy cheap High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing from wholesalers
    • Buy cheap High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing from wholesalers
    • Buy cheap High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing from wholesalers

    High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing

    Ask Lasest Price
    Model Number : SXCY
    Certification : CE/SGS/EMS/ISO 9001
    Delivery Time : 30 Working Days
    Brand Name : Sansion Power
    Payment Terms : L/C,T/T
    • Product Details
    • Company Profile

    High Voltage Lightning Impulse Generator Test System Custom-Built for Power Substation Transformer and High Voltage Cable Insulation Type Testing

    200kV Automatic Lightning Impulse Voltage Generator

    Product Description

    The automatic lightning impulse voltage generator is designed for full-wave lightning impulse tests on electrical products rated 10kV and below. It is also suitable for impulse withstand testing of insulators and synthetic insulating materials.

    Product Features

    The control system uses a Mitsubishi FX2N series programmable logic controller. It supports manual control, fully automatic operation, and programmed control.

    The main and auxiliary operating units use graphical human-machine interface displays. The control system can connect to a computer through an RS232 interface for computer-based operation using dedicated software.

    Two-core optical fiber communication transmits control commands and equipment status feedback, helping reduce electromagnetic interference. Charging voltage, charging time, triggering, polarity switching, and protection settings can be managed through the control system.

    Equipment Components

    • Lightning Impulse Voltage Generator
    • Main Capacitors
    • Wavefront Resistors and Wavetail Resistors
    • Charging Resistors and Protective Resistors
    • Automatic Control System
    • High-Voltage Triggering System
    • Automatic Grounding and Safety Interlock System

    Additional Control Functions

    • Charging voltage and charging process indication
    • Charging voltage and charging time input via the LCD panel
    • Automatic or manual triggering and charging control
    • Charging voltage polarity switching
    • Audible alarm control
    • Selectable dynamic charging protection and configurable static charging protection
    • Equipment status indication, including self-breakdown, failure to trigger, charging abnormality, and stable charging

    Control System Technical Parameters

    Parameter

    Specification

    Charging Voltage Setting Range

    0–200.0 kV

    Maximum Charging Voltage

    100 kV

    Charging Time Adjustment

    30–180 s

    Charging Voltage Instability

    ≤ ±1%

    Trigger Delay

    0–1 s

    Chopping Delay

    2–6 μs

    Trigger Pulse Voltage

    Above 10 kV

    Trigger Pulse Rise Time

    Less than 100 ns

    Trigger Polarity

    Switchable

    Impulse Count Setting

    1–999

    Frequently Asked Questions

    Q1: Which controller is used in the system?

    A: The control system uses a Mitsubishi FX2N series programmable logic controller.

    Q2: Can operators control the system manually?

    A: Yes. Manual, fully automatic, and programmed control modes are available.

    Q3: Can the system connect to a computer?

    A: Yes. It supports an RS232 computer interface and dedicated control software.

    Q4: How does the system reduce electromagnetic interference?

    A: It uses two-core optical fiber communication for control commands and equipment status feedback.

    Q5: Can charging voltage polarity be changed?

    A: Yes. The control system supports charging voltage polarity switching.